Electromagnetic flow meter failure-no pulse output
Fault point: Converter Test tool. Verification scheme. 1. Confirm if there is a pull-up resistor at the site 2. Whether there is the voltage at the pulse acquisition end 3. Check if the wiring is correct Test result: 1. 1. No pull-up resistor 2. No voltage 3. Wrong wiring Treatment solution: 1. 1. Pull up […]