Can You Coil a Ground Wire? Grounding Best Practices for Industrial Instrumentation - Just Measure it

Can You Coil a Ground Wire? Grounding Best Practices for Industrial Instrumentation

On many industrial sites, electricians and instrument technicians leave extra length in grounding wires by coiling them into neat loops. The reasoning seems practical: the spare cable provides flexibility for future maintenance, prevents the wire from being pulled tight, and often makes the installation look organized.

But is it actually good practice to coil a grounding conductor?

In most industrial grounding applications, the answer is no.

Grounding and bonding conductors should generally be installed as short and straight as practical, with unnecessary loops, coils, and sharp bends avoided. This becomes particularly important in lightning protection, surge protection, instrumentation, and other applications involving fast transient currents.

The reason is not simply resistance.

It is also about inductance and impedance.

1. Why Should Grounding Conductors Be Short and Straight?

A grounding conductor is intended to provide a low-impedance path for fault currents, static charges, surge currents, and other unwanted electrical energy.

For ordinary DC or low-frequency conditions, we often focus primarily on conductor resistance.

However, during a lightning strike or fast electrical transient, the situation is different.

The impedance of a conductor can be expressed conceptually as:

Z = R + jωL

where:

  • R = conductor resistance
  • L = conductor inductance
  • ω = angular frequency
  • Z = total impedance

As the frequency content of a transient increases, the inductive component becomes increasingly important.

This is why a grounding conductor that appears perfectly acceptable from a DC resistance perspective may perform much less effectively during a fast surge.

The practical rule is therefore simple:

Keep grounding conductors short, direct, and free from unnecessary loops.

2. What Happens When a Ground Wire Is Coiled?

When a conductor is deliberately formed into multiple loops or a tight spiral, its inductance increases.

In simple terms, the installation begins to behave more like an inductor than a straight conductor.

For normal 50/60 Hz protective grounding, a few loose bends do not automatically make the grounding system ineffective.

However, under fast transient conditions—such as lightning, switching surges, or electromagnetic disturbances—the increased inductance can produce a larger voltage drop along the grounding path.

The basic relationship is:

V = L × di/dt

This equation is extremely important when discussing grounding.

Lightning and surge currents can change extremely rapidly. Even when the grounding conductor has very low DC resistance, a high di/dt combined with conductor inductance can create a significant transient voltage.

Therefore, unnecessary loops should be avoided.

3. Resistance Is Not the Only Concern

Coiling also normally means using more conductor than necessary.

Because conductor resistance increases with length:

R = ρL/A

where:

  • ρ = conductor resistivity
  • L = conductor length
  • A = conductor cross-sectional area

additional cable length produces additional resistance.

In many installations, the resistance added by a few extra loops may be relatively small. Therefore, it would be misleading to claim that a small coil automatically causes grounding failure.

The more important engineering concern—particularly for lightning and surge currents—is usually the increase in inductive impedance.

That distinction is important.

4. 50/60 Hz Protective Grounding vs. Lightning and Surge Grounding

Not all grounding applications behave in exactly the same way.

Protective Earthing

Protective earthing is primarily intended to keep exposed conductive parts at a safe potential and provide a path for fault current so that protective devices can operate correctly.

For these systems, conductor size, continuity, connection quality, fault-current capability, and compliance with applicable electrical standards are critical.

A loose bend or small amount of additional length does not automatically make protective earthing ineffective.

Nevertheless, unnecessarily long or tightly coiled conductors should still be avoided.

Lightning and Surge Grounding

Lightning is a very different situation.

Lightning currents have extremely fast rise times and contain substantial high-frequency components. Under these conditions, conductor inductance becomes much more significant.

A long, tightly coiled, or unnecessarily indirect grounding conductor can create a substantial transient voltage difference.

For lightning and surge protection:

Shorter and straighter is generally better.

This is also one reason surge protective devices (SPDs) should normally be connected with short conductors rather than long loops of wire.

5. Why Is This Important for Industrial Instrumentation?

Industrial plants contain large numbers of sensitive electronic instruments, including:

  • Electromagnetic flowmeters
  • Radar level transmitters
  • Pressure transmitters
  • Temperature transmitters
  • PLC systems
  • DCS systems
  • Remote I/O modules
  • Variable-frequency drives
  • Signal isolators
  • Surge protection devices

Many of these devices operate using low-level analog or digital signals.

Typical examples include:

  • 4–20 mA
  • HART
  • RS485
  • Modbus RTU
  • Pulse/frequency signals
  • Low-level sensor signals

Poor grounding practices can contribute to electromagnetic interference, unstable signals, communication errors, and reduced surge protection performance.

For instrumentation systems, grounding should therefore not be treated simply as “connecting a green/yellow wire somewhere.”

The routing, length, bonding arrangement, shielding philosophy, and grounding architecture can all matter.

6. Can You Leave Extra Length in a Ground Wire?

Sometimes extra conductor length is necessary.

A common example is a bonding conductor connected to a movable control cabinet door.

The conductor needs enough flexibility to allow the door to open and close without placing mechanical stress on the terminals.

In this situation, additional length can be provided using a smooth, large-radius bend.

The key difference is:

Acceptable:

A gentle curve providing sufficient mechanical movement.

Avoid:

Multiple tight loops or a compact spiral coil.

Always follow the applicable electrical standard, project specification, equipment manufacturer’s instructions, and minimum bending-radius requirements for the conductor being used.

7. Avoid Daisy-Chaining Equipment Ground Connections

Another common field mistake is connecting several instruments or devices in series:

Instrument A → Instrument B → Instrument C → Ground

This arrangement creates several potential problems.

If an intermediate connection becomes loose, corroded, or disconnected, downstream equipment may lose its intended grounding connection.

A better arrangement, where required by the applicable grounding design, is to connect individual equipment grounding or bonding conductors directly to the designated grounding bar or bonding network.

Conceptually:

Instrument A → Ground Bar

Instrument B → Ground Bar

Instrument C → Ground Bar

This approach reduces dependence on intermediate connections and makes inspection and maintenance easier.

The exact grounding topology should always follow the applicable electrical code and the project’s instrumentation grounding philosophy.

8. Grounding in Hazardous Areas Requires Extra Attention

Grounding and bonding become even more important in chemical plants, oil and gas facilities, tank farms, loading systems, and other hazardous locations.

In these environments, proper bonding and grounding may be required to control:

  • Fault currents
  • Static charge accumulation
  • Potential differences between conductive objects
  • Lightning-induced currents
  • Electrical transients

It is important, however, not to oversimplify the issue.

A coiled conductor does not necessarily mean that static electricity suddenly “cannot discharge.”

The engineering principle is that bonding and grounding paths should maintain appropriate electrical continuity and sufficiently low impedance for their intended purpose.

Unnecessary conductor length, poor terminations, corrosion, loose connections, and inappropriate routing should therefore all be avoided.

9. Four Practical Rules: Short, Straight, Adequate, Secure

A useful way to remember good grounding practice is:

Short

Use the shortest practical route between the equipment and the designated grounding or bonding point.

Avoid unnecessary spare cable.

Straight

Avoid tight loops, spiral coils, and unnecessary bends.

This is especially important for lightning and surge-current paths.

Adequate

Select conductor material and cross-sectional area according to the applicable standard, fault-current requirements, equipment specification, and installation environment.

Do not assume that one conductor size is suitable for every grounding application.

Secure

Grounding is only as reliable as its connections.

Use appropriate terminals and connection methods, and protect connections against loosening, oxidation, and corrosion.

A large grounding conductor with a poor termination is still a poor grounding connection.

10. Common Grounding Mistakes in Industrial Installations

During installation and commissioning, watch for these common problems:

  • Ground wires tightly coiled to store spare length
  • Excessively long grounding conductors
  • Unnecessary loops and sharp bends
  • Loose or poorly crimped terminals
  • Corroded grounding points
  • Multiple devices improperly daisy-chained
  • Inadequate conductor cross-section
  • Confusion between protective earth, instrument earth, and signal/shield grounding
  • Long SPD grounding connections
  • Cable shields grounded without following the system’s EMC design

Some of these problems may appear minor during normal operation.

Their significance can become much greater during a ground fault, lightning event, switching transient, or severe electromagnetic disturbance.

11. A Special Note About Cable Shields

Grounding a cable shield and grounding an equipment enclosure are related topics, but they are not necessarily the same thing.

For example, instrument signal cable shields may be grounded at one end or both ends depending on:

  • Signal type
  • Frequency
  • EMC requirements
  • Equipotential bonding design
  • Manufacturer recommendations
  • Plant grounding philosophy

Therefore, the simple rule “never create a ground loop” should not be applied blindly to every industrial instrumentation system.

Modern industrial EMC design requires consideration of the complete system rather than one isolated conductor.

12. Practical Grounding Checklist

Before commissioning an instrument or control system, check the following:

  • Is the grounding conductor as short as practical?
  • Are unnecessary loops and coils avoided?
  • Are bends smooth rather than tightly formed?
  • Is the conductor cross-section appropriate?
  • Are terminals properly crimped and tightened?
  • Are grounding surfaces clean and electrically conductive?
  • Is corrosion protection adequate?
  • Are grounding conductors routed according to the project specification?
  • Are surge protective device connections kept short?
  • Are cable shields terminated according to the system’s EMC design?
  • Are equipment grounding and instrument signal grounding being treated correctly?
  • Does the installation comply with applicable electrical and hazardous-area requirements?

A few minutes spent checking these details can prevent difficult troubleshooting later.

Conclusion

So, should a grounding wire be coiled?

As a general industrial practice, unnecessary tight coils and spiral loops should be avoided.

The objective of grounding is not simply to achieve continuity when measured with a multimeter. A good grounding system should provide a reliable, appropriately low-impedance path under the electrical conditions for which it was designed.

For ordinary protective earthing, a small amount of extra conductor length does not automatically cause grounding failure.

But for lightning protection, surge protection, high-frequency transients, and sensitive industrial instrumentation, conductor inductance and routing become increasingly important.

Remember the practical principle:

Keep grounding conductors short, direct, appropriately sized, and securely connected.

When additional length is required for mechanical movement, use a smooth bend rather than a tight coil.

Good grounding is often invisible during normal operation.

Its value becomes obvious when something goes wrong.