Turbine flowmeter failure – 485 communication not working
July 6, 2022
Default address 001, baud rate 9600, n without parity, 8 bits of data, 1 bit of stop Is the instrument...
Read More
Turbine flow meter fault – no pulse output
July 5, 2022
● Pulse mode and pulse equivalent can be modified in the parameters, refer to the manual for details ● Pulse...
Read More
Turbine flowmeter fault – current zero point drift
July 4, 2022
● The blue potentiometer can be adjusted by unscrewing the front cover directly; see pictureLeft zero, right full4mA potentiometer on...
Read More
Turbine flowmeter fault – screen does not light up
July 3, 2022
● Measure if the voltage supply to the instrument is normal or if the battery is charged ● Consider whether...
Read More
Turbine flowmeter fault – current output abnormal
July 2, 2022
(1) Three-wire current, current output is not normal: ● Pay attention to the wiring: 24V, COM (GND), IOUT ● Measure...
Read More
Gas turbine flow meter fault-485 communication problems or no communication
July 1, 2022
The default address of the instrument is 001, baud rate 9600, n without checksum, 8 bits of data, 1 bit...
Read More
Gas turbine flow meter fault-fast flow display
June 30, 2022
Whether the customer has moved the parameters Is the installation in accordance with the requirements Whether the flow rate is...
Read More
Gas turbine flow meter fault-Slow flow display
June 29, 2022
● Whether the customer has set the parameters ● Is the installation in accordance with the requirements ● Whether the...
Read More
Turbine flow meter fault-Abnormal temperature/pressure display
June 28, 2022
Abnormal instrument temperature displayIf the temperature display is abnormally high when the battery is powered, the battery is dead.If the...
Read More
Vortex flow meter fault -display 0 when meter has flow
June 27, 2022
Ask if the flow rate at the site is lower than the lower limit, then change the small flow rate...
Read More
Vortex flow meter fault-Incorrect flow rate display
June 26, 2022
● Check that the temperature and pressure of the instrument are displayed properly ● Ask the customer about the inaccuracy...
Read More
Vortex flow meter fault- 485 communication cann’t connected
June 25, 2022
485 communication cannot be connected The parameter confirmation function is selected for the 485 functions refers to the manual The...
Read More
Vortex flow meter fault – abnormal current output
June 24, 2022
The current output is not normal (1) Three-wire current, current output abnormal ● Pay attention to the wiring: 24V, COM,...
Read More
Turbine flowmeter failure-Abnormal temperature/pressure display
June 23, 2022
Abnormal temperature display ● If the temperature display is abnormally high when the battery is powered, the battery is dead...
Read More
Turbine flowmeter failure – flowmeter display too fast or too slow
June 22, 2022
The flow meter displays fast ● Whether the customer has set the parameters ● If the installation is in accordance...
Read More
Vortex flow meter fault-No equivalent output from the meter
June 21, 2022
● Pulse mode and pulse equivalent can be modified in the parameters, refer to the manual for details ● Pulse...
Read More
Vortex flow meter fault – no pulse output
June 20, 2022
No pulse output from the flow meter. ● Pulse mode and pulse equivalent can be modified in the parameters, refer...
Read More
Electromagnetic flow meter failure-no pulse output
June 19, 2022
Fault point: Converter Test tool. Verification scheme. 1. Confirm if there is a pull-up resistor at the site 2. Whether...
Read More
Electromagnetic flow meter failure – inaccurate flow (converter)
June 18, 2022
Fault point: inaccurate flow Fault point: Converter Troubleshooting solution. Test the internal parameters of the meter head for the correctness...
Read More
Electromagnetic Flow Meter Failure-Inaccurate flow (sensor)
June 17, 2022
Fault point: SensorTroubleshooting solution.Correct installation positionTest result.The mounting position does not meet the requirementsTreatment solution.Replace the mounting position (Appendix 5)Appendix...