Vortex flow meter fault- 485 communication cann't connected - Just Measure it

Vortex flow meter fault- 485 communication cann’t connected

485 communication cannot be connected

  • The parameter confirmation function is selected for the 485 functions refers to the manual
  • The default address of the instrument is 001, baud rate 9600, n without parity, 8 bits of data, 1 bit of stop
  • Is the instrument wired correctly, connect 24V COM 485A 485B, battery power supply and two-wire system do not support 485 functions, confirm 24V power supply is normal
  • The instrument communication is based on the MODBUS RTU protocol.
  • Communication register address needs to be offset by 1 bit if using a software device such as a PLC, e.g. 0004, then use 0005
Share This Story, Choose Your Platform!

Contact Us

    Please prove you are human by selecting the plane.

    Leave a Comment

    Your email address will not be published. Required fields are marked *