Under the condition that the range Q has been determined, the size of the flowmeter diameter D can be determined according to the range of the above-mentioned flow rate V, and its value is calculated by the following formula:
Q=πD2V/4
Q: Flow rate (m3/hr) D: Pipe inner diameter V: Flow velocity (m/h)
The range Q of the electromagnetic flowmeter should be greater than the expected flow value, and the normal flow value should be slightly greater than 50% of the flowmeter’s full scale.
◆Reference flow range
Diameter(mm) | Flow rate(m3/h) | Diameter(mm) | Flow rate(m3/h) |
φ15 | 0.06~6.36 | φ450 | 57.23~5722.65 |
φ20 | 0.11~11.3 | φ500 | 70.65~7065.00 |
φ25 | 0.18~17.66 | φ600 | 101.74~10173.6 |
φ40 | 0.45~45.22 | φ700 | 138.47~13847.4 |
φ50 | 0.71~70.65 | φ800 | 180.86~18086.4 |
φ65 | 1.19~119.4 | φ900 | 228.91~22890.6 |
φ80 | 1.81~180.86 | φ1000 | 406.94~40694.4 |
φ100 | 2.83~282.60 | φ1200 | 553.90~55389.6 |
φ150 | 6.36~635.85 | φ1600 | 723.46~72345.6 |
φ200 | 11.3~1130.4 | φ1800 | 915.62~91562.4 |
φ250 | 17.66~176.25 | φ2000 | 1130.4~113040.00 |
φ300 | 25.43~2543.40 | φ2200 | 1367.78~136778.4 |
φ350 | 34.62~3461.85 | φ2400 | 1627.78~162777.6 |
φ400 | 45.22~4521.6 | φ2600 | 1910.38~191037.6 |