Magnetic flow meter flow tube requirements
Magnetic flow meter Straight pipe: upstream≥5D, downstream≥3D. Insertion type entrance ≥10D, exit ≥5D Valve: Flowmeter installed behind the valve, flow meter upstream ≥10, Downstream≥5D Front of right-angle turn: Upstream ≥10, Downstream≥5D Behind of right-angle turn: Upstream ≥10, Downstream≥5D Horizontal installation: The inner diameter of the pipe should be the same as the inner diameter of […]