Turbine flowmeter fault – flow indication when not running

 ● Whether it is an industrial frequency disturbance (50HZ), characteristic: a value is displayed that does not change; this value can be calculated according to the following formula q—instantaneous flow rate (m3/h) f — frequency (HZ) K — coefficient (times/m3) ● Whether the wiring is laid in a line slot with strong electricity (220V or […]

Turbine flowmeter fault – flow indication when not running Read More »

Turbine flow meter fault-Abnormal temperature/pressure display

Abnormal instrument temperature display If the temperature display is abnormally high when the battery is powered, the battery is dead. If the temperature display is below zero or much lower, the circuit board temperature chip is damaged, return the circuit board to the factory or send a replacement board. Use a multimeter to measure the

Turbine flow meter fault-Abnormal temperature/pressure display Read More »