Why Vortex Flow Meters Are Often Misunderstood — The Real Reasons Behind Their Declining Popularity - Just Measure it

Why Vortex Flow Meters Are Often Misunderstood — The Real Reasons Behind Their Declining Popularity

Vortex flow meters have long been appreciated for their wide applicability, no moving parts, and reasonable cost. They are commonly used for steam, compressed air, gases, and clean liquid measurement.

However, in many industrial sites, vortex meters are often described as “unstable, inaccurate, or difficult to maintain.”
In most cases, these problems do not come from the instrument itself, but from selection, installation, and application mismatches.

This article clarifies the real performance boundaries of vortex flow meters and explains how to select, install, and maintain them correctly — using practical formulas and real-world cases.

1. Core Principle: Vortex Generation and Frequency

A bluff body inside the flow channel generates alternating vortex shedding.
The vortex frequency f is proportional to the fluid velocity v:

 

f=Stvdf = \frac{St \cdot v}{d}

 

Where:
St – Strouhal number (constant for given Re range)
d – Diameter of the bluff body

Therefore:

Flow measurement accuracy heavily depends on stable vortex formation.
Anything that changes flow stability will directly affect measurement.

2. Correct Selection Is the Foundation

2.1 Match Measuring Range to the Application

The actual operating flow must fall within the meter’s 20%–80% of full-scale range (high-accuracy products can extend to 10%–90%).

  • Below 20%: vortex signals weaken → meter displays zero or fluctuates

  • Above 80%: vortex may distort → sensor overload / long-term drift

Full-scale range selection rule:

 

Full ScaleMax Flow0.8andFull ScaleMin Flow0.2\text{Full Scale} \ge \frac{\text{Max Flow}}{0.8} \quad \text{and} \quad \text{Full Scale} \le \frac{\text{Min Flow}}{0.2}

 

If no full-scale meets both — pipe size must be reduced.

2.2 Pipe Diameter Must Match Flow Velocity

Vortex meters require sufficient flow velocity to generate stable vortices.

MediumRecommended Velocity
Liquid0.5 – 10 m/s
Gas / Air5 – 60 m/s
Steam20 – 70 m/s

Too low → vortex cannot form → 0 reading / unstable
Too high → high noise/vibration → signal distortion

If velocity is too low in a large pipeline:
Use concentric reducers to downsize to a smaller meter.

2.3 Material and Process Compatibility Checklist

ConditionSelection Requirement
Temperature up to 300℃Standard vortex meter
High temperature 300–450℃High-temperature probe & extended neck
Corrosive fluids316L or Hastelloy sensor body
High viscosity (>10 mm²/s)Not recommended (vortex weakens)

3. Installation Determines Stability

3.1 Straight Pipe Length Matters

To ensure uniform flow profile:

Upstream (Inlet)Downstream (Outlet)
≥ 10D≥ 5D

If upstream has valves, elbows, pumps → increase to 15D.

3.2 Use Concentric Reducers When Reducing Pipe Size

  • Only concentric reducers are acceptable

  • Eccentric reducers create asymmetric flow → major error

Standard requirement:

Reducer Length1.5Dsmaller pipe\text{Reducer Length} \ge 1.5D_{\text{smaller pipe}}

3.3 Installation Direction

  • Horizontal pipe: sensor upward (avoid liquid accumulation)

  • Vertical pipe: flow must be bottom → top (guarantee full pipe)

4. Maintenance and Verification

ItemFrequencyKey Point
Sensor cleaningEvery 3–6 monthsRemove deposits to avoid frequency distortion
Cable and grounding checkMonthlyEnsure stable signal transmission
Zero-point checkAnnuallyNo flow → reading must be zero

5. Case Studies

Case 1 — Incorrect Range & Pipe Size

  • Pipeline: DN200

  • Actual flow: 8–35 m³/h (water)

DN200 velocity at 8 m³/h = 0.28 m/s → Too low → Vortex unstable

Solution:

  • Reduce to DN150

  • Select full-scale 0–50 m³/h

  • Result: reading stability improved, accuracy < ±2.5%

Case 2 — Wrong Reducer Causing Asymmetric Flow

  • Fruit juice pipeline using eccentric reducer

  • Error increases with flowrate (8–12%)

Solution:

  • Replace with standard concentric reducer

  • Add ≥15D upstream straight pipe

  • Result: error decreases to ±2.5%

6. Practical Conclusion

Vortex flow meters are not fading because they are inaccurate.
They become problematic when:

  • Flow range is mismatched

  • Flow velocity is too low

  • Incorrect reducers are used

  • Straight pipe requirements are ignored

When properly selected and installed, vortex meters are reliable, durable, and cost-effective — especially for steam, compressed air, and clean liquids.

However:

MediumRecommended Meter
Clean stable liquidVortex / Electromagnetic
SteamVortex (ideal choice)
Natural gas & compressed airVortex or Rotary / Differential pressure
Slurry / conductive fluidsElectromagnetic flow meter