Default address 001, baud rate 9600, n without parity, 8 bits of data, 1 bit of stop
Is the instrument wired correctly, connect 24V GND 485A 485B, battery power and two-wire system do not support 485 functions, confirm 24V power supply is normal
The instrument communication is based on the MODBUS RTU protocol, note that the instrument can read up to 6 words in a row.
Communication register address needs to be offset by 1 bit if using software devices such as PLC, e.g. 0001, then use 0002