Standard Operating Procedure for Differential Pressure Transmitters with 3-Valve Manifold

๐Ÿ›  Scope of Application

This procedure applies to the safe operation of differential or pressure transmitters equipped with a 3-valve manifold (comprising a High-Pressure Valve [H], Low-Pressure Valve [L], and Balance Valve [B]). Correct sequencing is essential to prevent diaphragm damage and ensure accurate pressure readings.

โš™๏ธ Fundamental Principle

Always protect the transmitter by using the balance valve to equalize pressure before applying or removing process pressure.
Never expose the diaphragm to sudden unidirectional overpressure!

โœ… Start-Up Procedure (Commissioning)

๐Ÿ”„ Initial State

  • High-Pressure Valve (H): Closed

  • Low-Pressure Valve (L): Closed

  • Balance Valve (B): Open โ†’ Equal pressure in both pressure chambers of the transmitter

๐Ÿ”ง Step-by-Step Instructions

  1. Open the Low-Pressure Valve (L)

  2. Close the Balance Valve (B)

  3. Open the High-Pressure Valve (H)

๐Ÿ“Œ Operation Mnemonic

Open L โ†’ Close B โ†’ Open H

โ›” Shutdown Procedure (Decommissioning)

๐Ÿ”ง Step-by-Step Instructions

  1. Close the High-Pressure Valve (H)

  2. Open the Balance Valve (B)

  3. Close the Low-Pressure Valve (L)

๐Ÿ“Œ Operation Mnemonic

Close H โ†’ Open B โ†’ Close L

๐Ÿ”’ Final State

  • High-Pressure Valve (H): Closed

  • Low-Pressure Valve (L): Closed

  • Balance Valve (B): Open โ†’ The transmitter is safely isolated and pressure-balanced

โ— Key Safety Notes

โš ๏ธ Perform All Operations Slowly

Sudden opening or closing of valves can cause pressure spikes, which may rupture the diaphragm inside the transmitter.

โš™๏ธ Balance Valve Is Critical

  • During Start-Up:

    • Open L before closing B โ†’ Avoid high-pressure shock to the low-pressure chamber

  • During Shutdown:

    • Close H before opening B โ†’ Prevent residual pressure from damaging the system

๐Ÿงช Handling Hazardous Media

  • For steam or corrosive fluids:

    • Depressurize first and wear proper personal protective equipment (PPE)

  • For crystallizing media:

    • Flush the impulse lines after shutdown to prevent clogging

๐Ÿง  Summary of Mnemonics

ProcedureSequence (Mnemonic)
Start-UpOpen L โ†’ Close B โ†’ Open H
ShutdownClose H โ†’ Open B โ†’ Close L

๐Ÿ“Œ We recommend posting this mnemonic chart near the transmitter for quick reference and safer operation.