- Product Overview
This series of radar level meter adopted 26G high frequency radar sensor, the maximum measurement range can reach up to 80 meters. Antenna is optimized further processing, the new fast microprocessors have higher speed and efficiency can be done signal analysis, the instrumentation can be used for reactor, solid silo and very complex measurement environment.
- Principle
Radar level transmitter antenna microwave pulse is narrow, the downward transmission antenna. Microwave exposure to the medium surface is reflected back again by the antenna system receives, sends the signal to the electronic circuit automatically converted into level signals (because the microwave propagation speed, electromagnetic wave to reach the target and the reflected back to the receiver this time is almost instantaneous).
A Range set
B Low adjustment
C High
D Blind area
Datum measurement: Screw thread bottom or the sealing surface of the flange.
Note: Make sure the radar level meter the highest level cannot enter the measuring blind area (Figure D shown below).
- The characteristics of 26G radar level meter:
- Small antenna size, easy to install; Non-contact radar, no wear, no pollution.
- Almost no corrosion, bubble effect; almost not affected by water vapor in the atmosphere, the temperature and pressure changes.
- Serious dust environment on the high level meter work has little effect.
- A shorter wavelength, the reflection of solid surface inclination is better.
- Beam angle is small, the energy is concentrated, can enhance the ability of echo and to avoid interference.
- The measuring range is smaller, for a measurement will yield good results.
- High signal-to-noise ratio, the level fluctuation state can obtain better performance.
- High frequency, measurement of solid and low dielectric constant of the best choice.
- Product Introduction
902
Application:Liquid
Measuring Range:30 meters
Process Connection:Thread, Flange
Medium Temperature:-40℃ ~ 250℃
Process Pressure:-0.1 ~ 4.0 MPa
Accuracy: ± 3mm
Protection Grade:IP67
Frequency Range: 26GHz
Signal Output:4… 20mA/HART (Two-wire / Four)
RS485/ Modbus
Explosion-proof Grade: Exia ⅡC T6 Ga
Exd ia ⅡC T6 Gb
- The Installation Requirements
- Installation guide:
Be installed in the diameter of the 1/4 or 1/6.
Note: The minimum distance from the tank
wall should be 200mm.
Note: ① datum
②The container center or axis of symmetry
- The top conical tank level, can be installed at
the top of the tank is intermediate, can guarantee
the measurement to the conical bottom.
- A feed antenna to the vertical alignment surface.
If the surface is rough, stack angle must be used
to adjust the angle of cardan flange of the antenna
to the alignment surface.
(Due to the solid surface tilt will cause the echo
attenuation, even Loss of signal.)
- Typical installation errors:
- Conical tankcannot be installed above the feed port.
Note: outdoor installation should adopt sunshade.
- Correct
- Error rainproof measures
- The instrument cannot be installed in the arched or domed roof intermediate. In addition to produce indirect echo is also affected by the echoes. Multiple echo can be larger than the real value of signal echo, because through the top can concentrate multiple echo. So cannot be installed in a central location.
- Correct
- Error
- There are obstacles affecting measurement needed reflection plate.
- Correct
- Error
- Height of nozzle:
Antenna extends into the tank
at least 10mm distance.
- The Electrical Connection
- The power supplyvoltage:
(4~20)mA/HART (Two wire system) The power supply and the output current signal sharing a two core shield cable. The supply voltage range see technical data. For intrinsically safe type must be a safety barrier between the power supply and the instrument.
(4~20)mA/HART(Four wire system) Separate power supply and the current signal, respectively using a two-core shielded cable. The supply voltage range see technical data.
RS485 / Modbus Power supply and Modbus signal line separate drespectively using a two-core shielded cable, the power supply voltage range see technical data.
- Connection mode:
- 24V two wire wiring diagram as follows:
- 220V four wire connection is as below:
- 24V RS485/Modbus wiring diagram as follows:
- Safety instructions:
- Please observe the local electricalcode requirements!
- Please comply with local requirements for personnel health and safety regulations.
All electrical components of instrument operation must be completed by the formal training of professionals.
- Please check the instrument nameplate to provide product specifications meet your requirements. Please make sure that the power supply voltage and instrument nameplate on the requirements.
- Protection grade:
This instrument meets the protection class IP66/67 requirements, please ensure the waterproof cable sealing head. The following diagram:
:
How to install to meet the requirements of IP67:
Please make sure that the sealing head is not damaged.
Please make sure that the cable is not damaged.
Please make sure that the cable for use with electrical connection specification.
Cable into the electrical interface before its curved downward, ensure that the water will not flow into the shell, see the①
Tighten the cable seal head, see the②
Please electrical interface will not use blind plug tight, see the③
- Instrument Commissioning
- There are three kinds of debugging method:
- Display / Keyboard
- Host debugging
- HART handheld programmer
- Display /Keyboard:
Please debug the instrumentation by four buttons on the display screen. There are three debug menu languages optional. After debugging is generally used only for display, through the glass window can read measured value very clearly.
Display / Keyboard
① Liquid crystal display(LCD)
② The key
- PC debugging:
Connected to PC by HART
① RS232 interface or USB interface
② Radar level meter
③ HART adapter
④ 250 Ω resistor
- HART handheld programmer:
① HART handheld programmer
② Radar level meter
③ 250 Ωresistor
- Structure Size(Unit: mm)
- The outer shell:
- Appearance size:
902
- Flange type:
- Technical Parameters
The outer shell
The seal between the shell and the shell cover Silicone rubber
Casing window Polycarbonate
The ground terminal Stainless steel
The power supply voltage
Two wire system
The standard type (16 ~ 26) V DC
Intrinsically safe (21.6 ~ 26.4) V DC
Power dissipation max 22.5mA / 1W Allowable ripple
– <100Hz Uss<lV – (100~100K) Hz Uss<l0mV
The cable parameters
Cable entrance / plug 1 M20xl.5 cable entrance
1 blind plug
Terminal Conductor cross section 2.5mm²
Output parameters
The output signal (4 ~ 20) mA/RS485
Communication protocol HART
Resolution 1.6μA
Fault signal Constant current output; 20. 5mA
22mA
3.9mA
The integral time (0 ~ 50) s, adjustable
Blind area the ends of the antenna
The maximum distance measurement 30 meters
Microwave frequency 26GHz
Communication interface HART communication protocol
The measurement interval about 1 second (depending on the parameter settings)
Adjust the time about 1 second (depending on the parameter settings)
Display resolution 1 mm
Working storage and transportation temperature (-40~100) ℃
Process temperature (the temperature of the antenna part)
902 (-40~250)℃
Pressure Max.4MPa
Seismic Mechanical vibration l0m/s², (10 ~ 150) Hz
- Meter Linearity
902
Emission angle Depending on the size of the antenna
-¢46mm 18°
-¢76mm 12°
-¢96mm 8°
-¢121mm 6°
Precision See chart
- Product Model Selection
- 902
License
P Standard (Non-explosion-proof)
I Intrinsically safe (Exia IIC T6 Ga)
G Intrinsically safe type, Flameproof (Exd (ia) IIC T6 Gb)
Process Connection / Material
G Thread G1½″A / Stainless Steel 304
N Thread 1½″ NPT / Stainless Steel 304
A Flange DN50 / Stainless Steel 304
B Flange DN80 / Stainless Steel 304
C Flange DN100 / Stainless Steel 304
Y Special Custom
Antenna Type / Material
A Horn Antenna Φ46mm / Stainless Steel 316L
B Horn Antenna Φ76mm / Stainless Steel 316L
C Horn Antenna Φ96mm / Stainless Steel 316L
Y Special Custom
Seal Up / Process Temperature
V Viton / (-40~150) ℃
K Kalrez / (-40~250) ℃
The Electronic Unit
2 (4~20) mA / 24V DC / Two wire system
3 (4~20) mA / 24V DC / HART two wire system
4 (4~20) mA / 220V AC / Four wire system
5 RS485 / Modbus
Shell / Protection Grade
L Aluminum / IP67
G Plastic/ IP65
Cable Line
M M 20×1.5
N ½″ NPT
Field Display/The Programmer
A Belt
X Without