Electromagnetic flow meter failure - no fluid flow in pipe with flow indication (transducer) - Just Measure it

Electromagnetic flow meter failure – no fluid flow in pipe with flow indication (transducer)

Fault point: no pipe running with flow indication

Fault point: Converter

Troubleshooting solution.

Test whether the parameter setting of the flow zero correction FS is equal to 0

Test result.

Example: FS = +002

The solution:

Close the front and rear valves in the full pipe state, and calibrate the flow zero point through the parameter setting of the meter head, for example, FS=+002, change the line below FS to -002

 

Share This Story, Choose Your Platform!

Contact Us

    Please prove you are human by selecting the house.