Diagnosing & Fixing Inaccurate Readings in Electromagnetic Flowmeters - Just Measure it

Diagnosing & Fixing Inaccurate Readings in Electromagnetic Flowmeters

Executive summary

Most accuracy problems come down to four buckets: installation, fluid properties, device faults, and external interference. Use the triage table below, then follow the corrective actions.

1) Rapid triage (symptom → likely cause → how to check → fix)

SymptomLikely causeHow to checkCorrective action
Reading drifts / unstableNot full pipe; air bubblesLook for gurgling, intermittent zero; inspect upstream ventsEnsure full pipe; add air vent upstream; throttle valve downstream
Consistently high/low vs. referenceWrong diameter/scale in converterCompare converter setup vs. actual line size/flow rangeRe-enter pipe ID, range; perform zero calibration (full pipe, no flow)
Intermittent spikesPoor grounding / VFD noiseMeasure ground loop; note proximity to VFDs/transformersSeparate protective grounds; ≤10 Ω; route cables away from noise sources
Near-zero on conductive serviceElectrodes fouledInspect electrodes; look for scale/oil filmsClean with soft cloth or mild acid compatible with material
Output saturates at maxFlow exceeds range; wrong K-factorCompare process flow vs. configured spanIncrease range or use larger meter; correct configuration
Reading only at high flowLow conductivity fluidCheck conductivity (>~5 µS/cm needed)Switch technology (e.g., ultrasonic) or adjust process chemistry
Random dropoutsCoil/lead faultsMeasure coil resistance (per datasheet, usually tens of Ω)Repair wiring; replace sensor/coil if out of spec

2) Installation issues (most common)

  • Electrodes not orthogonal to flow

    • Ensure the electrode axis is perpendicular to flow. On horizontal runs, keep electrodes on the horizontal centerline to avoid gas/slag accumulation. Re-align the body if needed. 

  • Pipe not running full

    • Re-grade pipe or relocate meter; add upstream air release and a downstream restriction/valve to maintain backpressure so the meter is always flooded. 

  • Poor grounding / bonding

    • Give the sensor and converter their own protective ground (separate rods if possible, spacing >5 m). Target ground resistance ≤10 Ω. Bond liners or grounding rings as specified.

3) Fluid property mismatches

  • Conductivity too low

    • Magmeters need a conductive medium (rule-of-thumb >~5 µS/cm). Oils and ultra-pure water may not work—use ultrasonic/Coriolis instead or change process chemistry if acceptable. 

  • Entrained gas or solids

    • Fit strainers/filters and gas separators; ensure straight, bubble-free approach. Schedule electrode cleaning every 3–6 months in fouling services. 

  • Excess viscosity / high velocity

    • For viscous media, use a larger bore to reduce velocity and shear layers; keep working velocity in the 20–80% of span sweet spot (typical max ≤ 10 m/s).

4) Device faults & misconfiguration

  • Electrode scaling or wear

    • Clean de-energized using compatible methods (e.g., mild acid for mineral scale; avoid attacking electrode material). Replace if pitted or eroded. 

  • Wrong converter parameters

    • Verify: line size, range, outputs (pulse/4–20 mA/RS-485), pipe material/lining settings. Do a zero trim with the pipe full and static. 

  • Coil/wiring issues

    • Check coil resistance (datasheet value, typically tens of ohms). Inspect connectors for looseness and moisture ingress; replace faulty parts.

5) External electromagnetic interference

Keep the meter/cables away from strong fields (VFDs, large motors/transformers). If relocation isn’t possible, use a grounded metallic shield enclosure and segregate signal cables from power. Maintain ≥2 m spacing where practical.

6) Commissioning & maintenance checklist

Before startup

  • ✅ Straight run and orientation verified; electrodes on horizontal axis for horizontal lines

  • ✅ Always-full condition ensured (vent upstream, valve downstream)

  • ✅ Independent protective grounds installed (≤10 Ω), shield drain grounded at one end

  • ✅ Converter parameters match nameplate and process (ID, range, output scaling)

  • ✅ Noise sources identified; cable routing separated from power/VFD trunks

Routine care

  • 🗓️ Inspect/clean electrodes every 3–6 months in fouling services

  • 🗓️ Verify zero (full pipe, no flow) quarterly or after maintenance

  • 🗓️ Periodically re-torque flanges and re-test ground resistance

Field test procedures (quick references)

  1. Zero check — Full pipe, pumps off, valves closed. Output should be 0 within spec. Adjust zero if drifted. 

  2. Coil continuity — Isolate and measure coil resistance; compare to spec. Replace if out of range. 

  3. Noise isolation — Temporarily power from a clean circuit, bypass VFD, or run on UPS to see if noise disappears. If yes, improve shielding/grounding and cable segregation

Share This Story, Choose Your Platform!

Contact Us

    Please prove you are human by selecting the cup.
    Translate »