Causes and Troubleshooting Procedures for Boiler Drum Differential Pressure Transmitter Deviations - Just Measure it

Causes and Troubleshooting Procedures for Boiler Drum Differential Pressure Transmitter Deviations

Abstract

The differential pressure (DP) transmitter for boiler drum level measurement is a critical instrument for ensuring safe and stable boiler operation. Deviations between actual water level and transmitter readings may lead to serious risks such as boiler dry-out, overfilling, or even turbine water hammer.
This document summarizes five major categories of deviation causes, provides a step-by-step troubleshooting guide, and highlights field cases to support maintenance, calibration, and safe operation.

1. Common Causes of Deviation

CategoryTypical SymptomsKey Impact
1. Abnormalities in balance vessel / impulse pipingBlockage by scale or sludge, condensation water not fully filled, leakage at impulse lines, freezing in winterFalse high / false low readings
2. Incorrect range or zero migration settingsWrong span configuration, migration set as opposite sign, 4–20 mA mapping reversedSystematic deviation in output
3. Hardware faults of transmitterDamaged diaphragm, signal module failure, unstable power supply, loose wiringOutput signal unstable, frozen, or absent
4. Abnormal boiler operating conditionsRapid pressure fluctuation, water level surges, carryover, poor water qualityDP reading unstable or delayed
5. Calibration drift / poor maintenanceLong-term zero drift, improper calibration method, lack of routine blow-offGradual systematic deviation

2. Troubleshooting Procedure (Step-by-Step)

The principle is “from simple to complex, from signal source to transmitter.”

Step 1: Initial On-Site Inspection

  • Verify true water level: Compare transmitter reading with local level gauge (quartz glass / two-color type).

  • Check boiler conditions: Ensure steam pressure and feedwater stable.

  • Inspect impulse lines and balance vessel:

    • Blow down lines, check for clogging or leakage (soap water bubble test).

    • Confirm condensation chambers are fully filled.

    • In winter, check for freezing.

Step 2: Parameter Verification

Access transmitter via HART communicator or DCS. Key items:

ParameterCorrect Setting (Example)Typical Error
Span (Range)-6 to +6 kPa (corresponding to -100 to +100 mm water level)0–12 kPa (output shifted by +6 kPa)
Zero migrationCalculated based on balance vessel height and condensate densityNot set (baseline offset)
Output mapping4 mA = lowest level (dry), 20 mA = highest level (full)Reversed mapping

Save and restart transmitter, then re-verify against local gauge.

Step 3: Hardware Diagnosis

  • Signal simulation: Inject standard DP values (e.g., -5/0/+5 kPa) and verify 4–20 mA correspondence.

  • Power supply check: Ensure 24 VDC ±10%.

  • Module diagnostics: Read fault codes (e.g., diaphragm overpressure, communication loss).

  • Spare unit replacement: Swap with a calibrated spare transmitter to confirm failure.

Step 4: Field Calibration

  • Stabilize boiler load before calibration.

  • Perform zero adjustment (balance valve open = zero DP).

  • Conduct span calibration by simulating full water and dry drum conditions.

  • Verify accuracy at three points (low, normal, high).

  • Acceptance: ≤±1 mm (level) or ±0.5% FS (DP).

Step 5: Long-Term Preventive Measures

  • Blow off impulse lines monthly.

  • Calibrate zero/span every 6 months; full-range calibration annually.

  • Add insulation/heat tracing to outdoor lines in winter.

  • Configure DCS compensation for pressure-dependent density changes.

  • Keep spare transmitters and balance vessel parts in stock.

3. Safety Precautions

  • Always follow boiler shutdown procedures before disconnecting lines.

  • Record all original parameters before calibration to prevent configuration loss.

  • Work with boiler and maintenance teams for welding or vessel replacement.

4. Field Case Studies

Case 1: Clogging by black deposits

  • Symptom: One drum transmitter output lower than others.

  • Cause: 1 mm orifice plate at flange blocked by black deposits.

  • Solution: Cleaning and reinstalling restored normal reading.

Case 2: Leakage at transmitter connection

  • Symptom: Large deviation between left and right side drum levels in winter.

  • Cause: Poor-quality gasket, improper reinstallation after antifreeze water drain.

  • Solution: Replaced gasket and re-tightened, restored accuracy.

Case 3: DCS deviation due to improper impulse line installation

  • Symptom: DCS level reading -50 mm, local gauge -330 mm.

  • Cause: Heat tracing installed incorrectly; negative impulse line leaking; DCS using “high-value selection” logic.

  • Solution: Corrected tracing, sealed leaks, recalibrated transmitters, and adjusted DCS logic.

Conclusion

Accurate boiler drum level measurement is fundamental for safe boiler operation. By systematically analyzing deviation causes, following structured troubleshooting steps, and implementing preventive measures, plant operators can significantly reduce false readings, improve safety, and extend transmitter service life.

Share This Story, Choose Your Platform!

Contact Us

    Please prove you are human by selecting the plane.
    Translate »