Electromagnetic Flow Meter Failure-Inaccurate flow (sensor)

Fault point: Sensor Troubleshooting solution. Correct installation position Test result. The mounting position does not meet the requirements Treatment solution. Replace the mounting position (Appendix 5) Appendix 5 Flowmeter correct installation and precautions. The length of the straight pipe section is best for the flowmeter before ≥ 10DN, the back end ≥ 5DN, when the

Electromagnetic Flow Meter Failure-Inaccurate flow (sensor) Read More »

Electromagnetic Flow Meter Failure-Without 485 communication

Fault point: Converter Detection tool: Test software Troubleshooting solution. 1. Confirm that the communication protocol matches the meter head 2. Use the test software to check if the communication is available Test results. 1. The protocol is the same, the parameters are set correctly 2. Test software cannot communicate with the meter head Treatment options:

Electromagnetic Flow Meter Failure-Without 485 communication Read More »

Electromagnetic flow meter failure-No display after power-on

Fault phenomenon: No display after power on Fault point: Converter Detection tool: Multimeter Verification program. 1. Detect whether the site voltage is normal 2. Detect whether the fuse, or lightning protection tube are normal 3. LCD line Test results:  1. Voltage within the normal range ±15% 2. Fuse tube damaged The lightning protection tube is

Electromagnetic flow meter failure-No display after power-on Read More »

Electromagnetic flow meter failure – unstable flow

Fault point: Sensor Verification program. 1. flowmeter installation position is correct 2. Whether there are media covering the electrode 3. Whether the flowmeter is grounded Test results. 1. Replace the installation position 2. The electrode is covered 3. No grounding Treatment options: 1. 1. Replace the installation position. 2. Clean the electrodes regularly 3. Instruct

Electromagnetic flow meter failure – unstable flow Read More »

Electromagnetic flow meter failure – no fluid flow in pipe with flow indication (transducer)

Fault point: no pipe running with flow indication Fault point: Converter Troubleshooting solution. Test whether the parameter setting of the flow zero correction FS is equal to 0 Test result. Example: FS = +002 The solution: Close the front and rear valves in the full pipe state, and calibrate the flow zero point through the

Electromagnetic flow meter failure – no fluid flow in pipe with flow indication (transducer) Read More »