Why the Sub-Meter Shows Flow but the Main Steam Flow Meter Reads Zero - Just Measure it

Why the Sub-Meter Shows Flow but the Main Steam Flow Meter Reads Zero

A Practical Troubleshooting Case Study

In industrial steam measurement systems, discrepancies between sub-meters and the main flow meter are not uncommon. One particularly confusing situation is when the branch flow meter shows a stable flow rate, while the main meter continuously indicates zero flow.

Is this a sensor failure?
A wiring problem?
Or is the issue hidden in system configuration?

This article presents a real on-site case study and explains how the root cause was identified.

1. Field Problem Description

At a thermal power plant of a petrochemical enterprise in Zibo, Shandong Province, saturated steam was supplied to three downstream users.

The steam metering system was configured as follows:

  • Main steam pipeline:

    • DN100 pipe

    • One orifice plate flow meter installed on the main line

  • Branch pipelines:

    • Three vortex flow meters installed on downstream branches

During operation:

  • Two vortex meters were no longer in service

  • One vortex flow meter was operating normally

  • Indicated flow rate: approximately 300 kg/h

However, the main orifice flow meter displayed zero flow for a long period, even though:

  • Temperature indication was normal

  • Pressure indication was normal

  • Installation position complied with standards

This raised a key question:

Why does the sub-meter show 300 kg/h while the main meter shows zero?

2. Instrument Configuration Overview

The main orifice flow meter was designed with:

  • Maximum flow rate: 0–10 t/h

  • Differential pressure range: 0–16 kPa

The vortex flow meter on the branch line showed:

  • Steam pressure: 0.81 MPa

  • Flow rate: 300 kg/h

From an installation perspective:

  • Differential pressure transmitter mounted on a horizontal pipe

  • Positive and negative impulse lines routed upward

  • Condensate pots installed at equal heights

  • Root valves were gate valves

No obvious installation error was observed.

3. Initial Diagnosis: Is the Instrument Faulty?

At first glance, the situation suggested a possible failure of the differential pressure transmitter.

However, after reviewing the configuration parameters, one critical setting attracted attention:

Low-flow cutoff (small signal suppression): 100 Pa

This parameter turned out to be the key.

4. Root Cause Analysis: Small Signal Cutoff

For differential pressure flow meters, low-flow cutoff is commonly applied to prevent unstable readings at very small differential pressures.

In this case:

  • Maximum flow rate (qₘₐₓ): 10 t/h

  • Low-flow cutoff differential pressure: 100 Pa

Based on calculation, this cutoff value corresponds to a flow rate of approximately:

790 kg/h

This means:

  • Any actual flow below 790 kg/h is treated as “zero” by the system

  • The real branch flow of 300 kg/h was entirely filtered out

Therefore:

The main flow meter was not faulty —
the actual flow was simply below the configured cutoff threshold.

5. Why Was the Cutoff Set Too High?

For standard single-range differential pressure flow meters, industry experience shows that:

  • A cutoff of 2% of maximum flow (2% qₘₐₓ) is generally reasonable

However, in this application:

  • The selected maximum differential pressure (ΔPₘₐₓ = 16 kPa) was relatively small

  • As a result, the corresponding cutoff differential pressure became extremely low

  • Even a slight imbalance in condensate pot height could significantly affect measurement

For example:

  • A height difference of only 0.7 mm between condensate pots

  • Could already generate a false differential pressure signal

This makes accurate low-flow measurement very difficult.

6. Importance of Proper Differential Pressure Range Selection

If a higher differential pressure range had been selected, for example:

  • ΔPₘₐₓ = 60 kPa

Then:

  • The cutoff differential pressure corresponding to 2% qₘₐₓ would increase to about 24 Pa

  • Low-flow resolution would improve significantly

  • Small signal suppression would be much easier to control

In short:

Choosing an excessively small ΔPₘₐₓ greatly reduces low-flow measurement accuracy.

7. Special Consideration for Non-Standard DP Flow Meters

For some non-standard differential pressure flow meters, such as:

  • Elbow flow meters

  • Annubar (averaging pitot tube) flow meters

The maximum differential pressure cannot be freely selected.

For example, when measuring saturated steam at 0.7 MPa using an averaging pitot tube:

  • At a maximum velocity of 30 m/s

  • ΔPₘₐₓ may be only about 1,620 Pa

In such conditions:

  • A condensate pot height difference of just 1 mm

  • Can generate a false flow reading of nearly 8% of maximum flow

This highlights how sensitive DP steam measurement systems can be.

8. Key Engineering Conclusions

This case demonstrates several important lessons:

  1. Zero reading does not always indicate instrument failure

  2. Low-flow cutoff settings must be reviewed carefully

  3. Differential pressure upper range selection is critical

  4. Small installation deviations can significantly affect low-flow accuracy

  5. Steam flow measurement requires system-level consideration, not only sensor selection

Conclusion

When discrepancies appear between main meters and sub-meters, engineers should not immediately suspect hardware faults.

Instead, attention should be directed to:

  • Flow range design

  • Differential pressure range selection

  • Low-signal cutoff configuration

In many cases, the issue lies not in the instrument itself, but in parameter design choices made during the initial engineering stage.

Share This Story, Choose Your Platform!

Contact Us

    Please prove you are human by selecting the plane.
    Translate »