Heat-Trace Cable Selection Guide - Just Measure it

Heat-Trace Cable Selection Guide

1) Define the Duty (Process Requirements)

  • Maintain temperature (Tₘ): e.g., anti-freeze (>0 °C) or process hold (50–100 °C).

  • Max exposure temperature (Tₑₓₚ): abnormal heat, upset, or external sources. Select jacket & cable class with T rating ≥ Tₑₓₚ.

  • Recommended cable type by duty

    • Self-regulating (SR): maintain ≤ ~130 °C; auto-throttles output, safer on overlaps.

    • Constant-watt (CW): single-/parallel-conductor; maintain ≤ ~150 °C (single-phase), higher on 3-phase; must use controller.

2) Size the Power (Compensate Heat Loss)

  • Estimate heat loss (q, W/m): function of pipe OD, insulation thickness/λ, ambient Tmin, wind, emissivity.

  • Match cable output: choose W/m @ Tₘ (e.g., 10/20/30/40 W/m). Use multiple runs or higher rating if q > one run’s output.

  • Length limits: CW has strict max circuit length (voltage/power dependent); SR is more forgiving but consider voltage drop. Segment long runs.

3) Check the Environment

  • Chemical/corrosion: select FEP/fluoropolymer or reinforced polyolefin jackets; protect braid/core from attack.

  • Moisture/ingress: target IP68 or better if buried/submerged; use sealed power/termination kits.

  • Hazardous area: require appropriate Ex certification (e.g., Ex d IIC T4 or per local code) and correct temperature class.

  • Mechanical abuse: choose armored or heavy-duty jacket; verify minimum bend radius (typ. ≥5×OD for SR, ≥10×OD for CW).

4) Match the Hardware (Pipe/Equipment)

  • Geometry: straights, bends, valves, flanges, tanks → affects layout (straight, helical wrap, multi-run).

  • Material: metal pipes conduct well; plastics may need higher W/m or closer wrap.

  • Specials: add extra length around valves/flanges (≈1.5–2× circumference). Allow slack for expansion joints (~1.2× expansion).

5) Power & Controls

  • Supply: 220 VAC common; some use 380 VAC. Match cable rating.

  • Control level: simple on/off thermostat vs. PID/remote monitoring with RTD/TC sensors and alarms.

  • Protection: RCD/GFCI ≤30 mA; proper circuit breakers per inrush/steady current of SR/CW.

6) Installation Rules (Do/Don’t)

Do

  • Fix with high-temp tape (e.g., aluminum) at 0.5–0.8 m spacing; keep runs evenly spaced for helical wraps.

  • Use certified power/tee/end-seal kits; bond braid to earth; verify earth ≤4 Ω.

  • Perform IR test before & after install, and a brief energized test before insulation (10–15 min).
    Don’t

  • Don’t over-bend, cross, or tightly overlap CW runs (hot spots).

  • Don’t drag on rough ground or across sharp edges; use pads at welds/angles.

  • Don’t bury junction/termination boxes under insulation; keep sensors accessible.

7) Commissioning Checklist

  • Cable model, W/m @ Tₘ, voltage, approvals match datasheet.

  • Circuit length within manufacturer max; voltage drop checked.

  • IR ≥ manufacturer minimum to ground and between conductors.

  • Controller setpoints & high-temp cutout verified; alarms tested.

  • Insulation thickness/material installed; weather jacketing sealed.

8) Alternative Heat-Maintenance Methods (Quick Comparison)

MethodHeat SourceCapexOpexControl AccuracyHeat TransferNotes
Steam tracingBoiler steamMidMid-HighLowLowRobust, high output; needs steam plant/piping.
Hot-water tracingPlant hot waterMidHighMidLowCan reuse low-grade heat; higher line losses, lower control.
Electric heat-traceElectricityHighLowHighHighPrecise, modular; needs proper design/controls.
Self-heating (“self-trace”)Process fluidLowMidMidMidOnly if process allows; limited range.

9) Example Spec Lines (Copy/Paste)

  • Cable: Self-regulating, 230 VAC, 20 W/m @ 10 °C, FEP over-jacket, tinned copper braid, T-rating ≥ Tₑₓₚ.

  • Circuit: Max run length per mfr; supply MCB + 30 mA RCD; junction/tee/end-seal kits per system vendor.

  • Controls: Wall-mount temperature controller with Pt100 sensor, high-temp cutoff, local alarm relay, Modbus/RS-485 (if required).

  • Install: Helical wrap on DN50, 45° valve add-length 1.5× circumference, tape at 0.6 m intervals, sensor placed on shaded, metal-to-metal contact point under insulation.

  • Test & Handover: IR and load tests logged; as-built route sketch; spare kit list.

Share This Story, Choose Your Platform!

Contact Us

    Please prove you are human by selecting the key.
    Translate »