Wiring Methods for RTD Temperature Transmitters - Just Measure it

Wiring Methods for RTD Temperature Transmitters

RTD (Resistance Temperature Detector) temperature transmitters are widely used in industrial automation for precise temperature measurement. Proper wiring is essential to ensure measurement accuracy and system stability. This guide explains wiring principles and methods for different RTD and transmitter configurations, including practical tips and troubleshooting advice.

1. 🔧 Basic Wiring Principles

1.1 Common RTD Types

  • Pt100 (Platinum 100Ω) is the most commonly used RTD sensor.

  • Accuracy classes:

    • Class A: ±0.15°C at 0°C

    • Class B: ±0.3°C at 0°C

  • RTDs may have 2, 3, or 4 wires, depending on the application and required precision.

1.2 Transmitter Power Supply

  • Most transmitters use 24V DC.

  • 2-wire transmitters: Power and signal share the same two wires.

  • 4-wire transmitters: Power and signal are independent.

1.3 Output Signal Types

  • 4–20 mA (most common, especially with 2-wire transmitters)

  • 0–5 V or 0–10 V (often in 4-wire transmitters)

  • Ensure compatibility with input terminals of control systems (PLC, DCS, etc.).

2. 🔌 Wiring Methods by Configuration

2.1 Three-Wire RTD + Two-Wire Transmitter (Most Common Setup)

RTD Terminals: 3 wires (commonly Red, Red, Black or labeled A, B, C)
Transmitter Terminals:

TerminalFunction
+24VPower supply positive
OUT+Signal output (same as +24V)
OUT-Common ground
R1, R2, R3RTD wiring terminals

Wiring Steps:

  1. Connect the two same-color wires (e.g., Red, Red) to R1 and R3.

  2. Connect the third wire (e.g., Black) to R2.

  3. Connect +24V and OUT- to the power supply.

  4. OUT+ goes to the signal input of the receiving device (e.g., PLC).

✅ This setup helps eliminate lead wire resistance error through compensation.

2.2 Two-Wire RTD + Four-Wire Transmitter

RTD Terminals: 2 wires only
Transmitter Terminals:

TerminalFunction
24V+, 24V-Power input
OUT+, OUT-Signal output
EXC+, EXC-Excitation (current source)

Wiring Steps:

  • Connect the two RTD wires to EXC+ and EXC-.

  • Power and signal wiring are completely independent.

⚠️ Note: Measurement accuracy is lower due to uncompensated lead resistance. Avoid in precision applications.

2.3 Four-Wire RTD + Four-Wire Transmitter (For High-Precision Use)

RTD Terminals: 4 wires

  • Two for excitation (current)

  • Two for sensing (voltage drop)

Transmitter Terminals:

TerminalFunction
EXC+, EXC-Excitation current supply
V+, V-Voltage measurement inputs

Wiring Steps:

  • Connect two excitation wires to EXC+ and EXC-.

  • Connect two sensing wires to V+ and V-.

✅ Ideal for long-distance or high-accuracy measurements, as voltage drop is measured directly, unaffected by wire resistance.

3. ⚠ General Wiring Tips

  • Cable Type: Use shielded twisted pair cables. Ground the shield at one end to reduce electromagnetic interference (EMI).

  • Wire Consistency: For 3-wire or 4-wire RTDs, make sure the same-color wires have equal resistance (usually factory-matched).

  • Polarity Check: Verify correct polarity before powering up. Incorrect wiring may damage the transmitter.

  • Short Circuit Test: Inspect for short circuits, especially under humid or dusty conditions.

  • Configuration: Some transmitters require manual or software configuration for:

    • RTD type (e.g., Pt100 or NTC)

    • Measuring range (e.g., -50°C to 150°C)

4. 🔄 Sample Wiring Diagram: 3-Wire RTD + 2-Wire Transmitter

Transmitter TerminalConnected ToDescription
+24VPower Supply +Supplies DC power
OUT+Signal Output to PLC/DCSTransmits 4–20 mA signal
OUT-Power Supply –Ground/common
R1RTD wire 1 (Red)First excitation line
R2RTD wire 2 (Black)Sensing line
R3RTD wire 3 (Red)Second excitation line

5. 🛠 Troubleshooting Guide

SymptomPossible CauseSuggested Action
No OutputPower disconnected or loose wiringCheck power supply and terminal contacts
Abnormal OutputWire short circuit, incorrect settings or groundingVerify wiring, shield ground, recheck config
No RTD ResponseSensor open circuit or damagedUse multimeter to check resistance (~100Ω for Pt100 at 0°C)

6. 📚 Final Notes

  • Always refer to the manufacturer’s manual for terminal labeling and pin definitions, as they may vary between brands.

  • Ensure proper grounding of the transmitter housing to reduce common-mode noise in industrial environments.

Share This Story, Choose Your Platform!

Contact Us

    Please prove you are human by selecting the plane.
    Translate »