Diagram of Pressure and Flow Sampling Point Locations - Just Measure it

Diagram of Pressure and Flow Sampling Point Locations

                       Gas pressure & flow                                                                                                             Liquid pressure flow

             Steam pressure                                                                                                                                     Steam flow

The installation positions of pressure measurement points on horizontal or inclined pipelines should comply with the following provisions:

1. When measuring gas pressure, the measurement point should be installed on the upper half of the pipeline.
2. When measuring liquid pressure, the measurement point should be installed within the range of 0-45° below the horizontal centerline of the pipeline.
3. When measuring steam pressure, the measurement point should be installed on the upper half of the pipeline or within the range of 0-45° below the horizontal centerline of the pipeline.

For the installation of throttling devices on horizontal or inclined pipelines, when the fluid is gas or liquid, the position of the pressure tapping point should comply with the provisions of clauses 1 and 2 of article 4.3.2 of this specification.

For the installation of throttling devices on horizontal or inclined steam pipelines, the position of the pressure tapping point should be within the range of a 45° angle from the horizontal centerline on the upper half of the pipeline.

Share This Story, Choose Your Platform!

Contact Us

    Please prove you are human by selecting the heart.