Electromagnetic flow meter failure – unstable flow

Fault point: Sensor

Verification program.

1. flowmeter installation position is correct

2. Whether there are media covering the electrode

3. Whether the flowmeter is grounded

Test results.

1. Replace the installation position

2. The electrode is covered

3. No grounding

Treatment options: 1.

1. Replace the installation position.

2. Clean the electrodes regularly

3. Instruct the customer on proper earthing.

The correct way to ground a flow meter

Grounding of the sensor installed on a plastic pipe or a metal pipe with an insulating tinted layer, lining, or lacquer layer on the inside.

When the sensor is installed on an insulated pipe, a short metal pipe or grounding ring must be installed at both ends and then connected with a wire to conduct the fluid.

When it is difficult to install a short metal pipe and grounding material on the sensor, the grounding electrode can be installed by drilling holes in the insulated pipe at both ends of the sensor.

The grounding electrode is made of corrosion-resistant alloy material and is connected to the sensor’s grounding screw with a wire.

As shown: Installation of the sensor on an insulated pipe.