Case study for power limited company - Just Measure it

Case study for power limited company

1. The first application field is flowing measurement from Limestone slurry tank common header to Absorber 1.2&3

Zero Instrument equipment supply.

2/4 wire Microprocessor-based Integral type Magnetic

Flowmeter, Electrode Material: SS316/Tantalum, Liner

Material: PFA, Process connection: Flange, Accuracy: 0.5% of

span, Output: 4-20mAHART, No. of Digit Display: 4 line LCD

Display(min), Electrical Connection: 1/2″ NPT(M), Housing

Protection: IP 65, Tube Size: Vendor to specify based on the

sizing calculation, Diagnostic: Lining erosion, electrode,

Recommended velocity: Vendor to specify, Straight length

requirement: Vendor to specify. Accessories: CS Counter

Flange, Gasket, Flow: 62 m3/hr, Pressure: 3.5 bar(g),

Temp: 35 deg C,Fluid Medium: limestone slurry. Line

Size: 100NB. Line MOC: ERW Pipe.Process connection: 4″ 150 lb

Flange, Inst. Cali. Range: 0-100 m3/hr

2.Flow measurement of process water to oxidation system

2 wire Microprocessor-based Integral type Magnetic

Flowmeter, Electrode Material: SS316L, Liner Material:

PTFE, Process connection: Wafer, Flow Tube MOC:

SS304,Accuracy: 0.5% of span, Output: 4-20mAHART, No. of

Digit Display: 4 line LCD Display(min), Electrical Connection:

1/2″ NPT(M), Housing Protection: IP 65, Tube Size: Vendor to

specify based on the sizing calculation, Diagnostic: Lining

erosion, electrode, Recommended velocity: Vendor to specify,

Straight length requirement: Line Size: 25NB, Flow: 5 m3/hr,

Pressure: 2 bar(g), Temp: 40 deg C, Pipe MOC: Carbon steel,Process

connection: 1″150lb Flange.Inst. Range: 0-15 m3/hr

3.Flow measurement at the make up header of Process water to Emergency quench water tank for Absorber 1, 2 &3

2 wire Microprocessor-based Integral type Magnetic

Flowmeter, Electrode Material: SS316, Liner Material: PTFE,

Process connection: Wafer, Accuracy: 0.5% of span, Output:

4-20mAHART, No. of Digit Display: 4 line LCD Display(min),

Electrical Connection: 1/2″ NPT(M), Housing Protection: IP

65, Tube Size: Vendor to specify based on the sizing

the calculation, Diagnostic: Lining erosion, electrode,

Recommended velocity: Vendor to specify, Straight length

requirement: Flow: 50 m3/hr, Pressure:5bar(g),Temp: 40 deg C,

Fluid Medium: Water. Line Size: 50 NB.Pipe Moc: Carbon steel,

Pipe Moc: Carbon steel,Process connection: 2″ Flange.Inst. Cali. Range: 0-50 m3/hr

Share This Story, Choose Your Platform!

Contact Us

    Please prove you are human by selecting the car.