Introduction: Is Daisy-Chained Instrument Grounding Acceptable?
Can several field instruments share a grounding conductor, or must every instrument have an independent connection to the plant grounding system?
This question has been debated among instrumentation engineers, electrical engineers, and maintenance technicians for many years.
Some engineers insist that every instrument must have an individual grounding connection. Others argue that multiple instruments can be connected through a common grounding path under certain conditions.
The answer is not simply yes or no.
Industrial instrument grounding serves several different purposes, including electrical safety, signal stability, electromagnetic interference reduction, electrostatic protection, and lightning protection.
A grounding arrangement that is acceptable for protective earthing may be unsuitable for signal reference grounding or cable shielding.
Recent revisions to China’s petrochemical instrumentation earthing standard, SH/T 3081-2025, have also brought renewed attention to this subject.
However, grounding requirements must always be evaluated according to the applicable electrical standards, hazardous area classification, equipment design, and manufacturer’s installation instructions.
This article explains the different types of instrument grounding, when daisy-chaining may be acceptable, and how to avoid common grounding-related measurement problems.
1. Why Is Grounding Important in Industrial Instrumentation?

Grounding is an essential part of industrial measurement and control system design.
A properly engineered grounding and bonding system supports:
- Personnel protection against electric shock.
- Reliable operation of electrical protection devices.
- Stable instrument signal transmission.
- Reduction of electromagnetic interference (EMI).
- Protection against electrostatic discharge.
- Lightning and surge protection.
- Reliable communication between field instruments and control systems.
Poor grounding can contribute to unstable measurements, communication failures, unexpected equipment damage, and potentially hazardous operating conditions.
For example, an electromagnetic flow meter may experience unstable readings because of inadequate process potential equalization. A pressure transmitter may produce a fluctuating output because of electrical interference. An RS485 communication network may experience intermittent communication failures because of excessive potential differences between devices.
These problems demonstrate why grounding should be considered part of the complete instrumentation system rather than simply an additional wire connected during installation.
2. Six Types of Grounding in Industrial Instrumentation
Before determining whether instruments can share a grounding conductor, engineers must first identify the purpose of the connection.
| Grounding type | Primary function | Typical applications |
|---|---|---|
| Protective Earthing (PE) | Electrical safety and fault protection | Instrument housings, cabinets, metallic enclosures |
| Functional Earthing (FE) | Electrical reference and functional performance | Signal circuits, instrument electronics, control systems |
| Cable Shield Grounding | Electromagnetic interference reduction | Analog signal cables, communication cables |
| Intrinsic Safety Earthing | Maintaining the required intrinsic safety architecture | Zener barriers and associated equipment |
| Electrostatic Earthing | Controlling electrostatic charge accumulation | Tanks, pipelines, loading systems |
| Lightning Protection Earthing | Providing an appropriate path for lightning and surge currents | Outdoor instruments, surge protection devices |
Although these grounding functions may ultimately connect to a common engineered plant grounding network, their connection methods and technical requirements can differ.
Separate grounding functions do not necessarily require separate earth electrodes.
The complete grounding architecture should be designed to maintain electrical safety, electromagnetic compatibility, and appropriate equipotential bonding.
3. Can Protective Earthing Be Daisy-Chained?
Protective earthing provides an electrical connection between exposed conductive parts and the protective grounding system.
If an insulation fault causes an instrument enclosure to become energized, the protective system must provide the conditions required for the appropriate protective device to operate.
Two commonly discussed connection arrangements are individual grounding connections and daisy-chained grounding connections.
3.1 Individual Protective Earthing
In an individual grounding arrangement, each instrument or enclosure has its own protective connection to an approved grounding busbar or grounding network.
This arrangement offers several advantages:
- Reduced dependence on neighboring instrument connections.
- Easier inspection and maintenance.
- Reduced risk of losing grounding continuity when another instrument is removed.
- Clearer identification of individual grounding paths.
Where practical and consistent with the project design, independent connections are often preferred for critical instruments.
3.2 Daisy-Chained Protective Earthing
In a daisy-chained arrangement, several instrument housings are connected through a shared grounding path.
Depending on the applicable standards and engineering design, this arrangement may be permitted under specific conditions.
However, its reliability depends on:
- Grounding conductor cross-sectional area.
- Fault current carrying capability.
- Terminal and connection reliability.
- Electrical continuity.
- Mechanical protection.
- Corrosion resistance.
- Maintenance and instrument removal procedures.
A significant disadvantage is that failure or removal of an intermediate connection may interrupt the protective path for downstream instruments.
Therefore, daisy-chaining should never be adopted simply to reduce installation costs or save grounding conductors.
The complete protective path must remain effective under the expected operating, fault, and maintenance conditions.
3.3 Engineering Example: SH/T 3081-2025
China’s revised petrochemical instrumentation earthing design standard, SH/T 3081-2025, replaced the 2019 edition and came into effect on July 1, 2026.
Published interpretations of the revised standard indicate that certain metallic equipment grounding connections may use a daisy-chained arrangement, with a recommended maximum of three consecutively connected instruments in the specified circumstances.
However, this should not be interpreted as a universal permission to connect any three instruments together.
The requirements apply within the scope of the relevant Chinese petrochemical engineering standard and must be interpreted together with the official standard text, approved project design, and other applicable safety requirements.
International projects may follow different national regulations, IEC standards, or customer specifications.
A reliable protective grounding arrangement is more important than simply complying with a numerical limit.
4. Functional Earthing and Signal Reference Grounding
Functional earthing is used to support the intended operation and electrical performance of equipment.
In instrumentation systems, it may provide a stable reference potential for analog signals, electronic circuits, and control equipment.
However, not every signal circuit requires a direct earth connection.
4.1 Single-Point Grounding
Single-point grounding is commonly used in certain low-frequency analog measurement systems.
The objective is to establish a controlled reference potential while reducing unwanted current caused by potential differences between grounding locations.
Typical applications may include certain:
- 4–20 mA signal circuits.
- Analog voltage signals.
- Low-level sensor circuits.
- Non-isolated control system inputs.
The grounding location must follow the system design and equipment instructions.
An additional grounding connection at an unintended location may create a ground loop or interfere with the measurement circuit.
4.2 What Is a Ground Loop?
A ground loop can occur when interconnected equipment has multiple conductive paths between grounding points at different electrical potentials.
These potential differences may drive unwanted current through signal references, shields, or other interconnecting conductors.
Possible symptoms include:
- Fluctuating analog signals.
- Unstable pressure readings.
- Temperature measurement deviations.
- Unexpected flow measurement noise.
- Intermittent communication failures.
Ground loops are particularly important in large industrial facilities where field instruments and control cabinets may be located far apart.
However, these symptoms are not proof of a ground loop. Other electrical and process-related causes must also be investigated.
4.3 Grounded vs. Floating Signal Circuits
Some industrial signal circuits are designed with galvanic isolation.
Depending on the equipment and system architecture, an isolated signal circuit may operate without a direct connection between its signal reference and earth.
Examples include:
- Isolated analog input modules.
- Galvanically isolated signal conditioners.
- Isolated transmitters.
- Certain isolated intrinsic safety interfaces.
A floating signal circuit should not be grounded arbitrarily.
Adding an unintended reference connection may defeat the benefits of isolation or create unexpected current paths.
Always distinguish between the grounding of the instrument enclosure and the grounding of the internal signal circuit.
5. Should Instrument Cable Shields Be Grounded at One End or Both Ends?

Cable shielding is used to reduce the influence of electromagnetic interference on signal and communication circuits.
One of the most common misconceptions in industrial instrumentation is that cable shields must always be grounded at only one end.
In reality, the appropriate shielding method depends on the signal frequency, communication system, equipment design, and plant bonding architecture.
5.1 Single-End Shield Grounding
Single-end shield grounding is commonly used for certain low-frequency analog instrumentation circuits.
In a typical arrangement, the shield is terminated at the designated grounding point, often on the control system side, while the opposite end is insulated from unintended contact.
Potential benefits include:
- Reduced low-frequency circulating shield currents.
- Controlled shield termination.
- Improved performance in suitable analog signal systems.
This arrangement may be appropriate for certain pressure, temperature, level, and flow transmitter circuits.
However, the actual termination method should follow the relevant instrument and control system documentation.
5.2 Both-End Shield Grounding
Both-end shield grounding may be required in certain communication networks and high-frequency electromagnetic compatibility applications.
At higher frequencies, the impedance of the shield connection becomes increasingly important.
A long grounding lead can reduce shielding effectiveness even when its DC resistance is low.
Proper low-impedance shield termination at both ends can improve electromagnetic compatibility in appropriately designed systems.
Typical applications may include:
- PROFIBUS communication networks.
- Certain industrial Ethernet systems.
- Variable frequency drive motor cables.
- Other high-frequency industrial communication systems.
Where significant potential differences exist between equipment locations, appropriate equipotential bonding or electrical isolation may also be required.
The cable shield must not be used as a substitute for a required protective or equipotential bonding conductor.
5.3 Selecting the Correct Shield Grounding Method
| Application | Typical grounding consideration |
|---|---|
| 4–20 mA analog signals | Single-end shielding is commonly used |
| RTD and thermocouple signals | Follow sensor and transmitter requirements |
| HART communication | Follow the analog loop and device requirements |
| RS485 / Modbus RTU | Follow the network and equipment grounding design |
| PROFIBUS | Both-end shielding is commonly specified |
| Industrial Ethernet | Follow network EMC and equipment requirements |
| VFD motor cables | Low-impedance termination at both ends is commonly required |
These are general engineering considerations rather than universal wiring instructions.
The correct grounding arrangement must follow the applicable system documentation.
6. Cable Shielding and Cable Armour Are Not the Same
Industrial instrument cables may contain both a conductive shield and metallic armour.
Although both are metallic components, they serve different purposes.
| Characteristic | Cable shield | Cable armour |
|---|---|---|
| Primary purpose | Electromagnetic interference reduction | Mechanical protection |
| Electrical function | Signal and EMC performance | May also support bonding or protective functions |
| Connection method | Depends on the signal and network architecture | Depends on cable construction and electrical safety requirements |
| Typical construction | Copper braid or metallic foil | Steel wire, steel tape, or other metallic armour |
For petrochemical plants, oil terminals, and hazardous areas, armoured cables are frequently used to provide additional mechanical protection.
The armour connection must be determined according to the electrical design, cable gland construction, hazardous area requirements, and applicable standards.
Do not automatically apply the single-end signal shield grounding rule to metallic cable armour.
7. Grounding Requirements in Hazardous Areas
Grounding is particularly important in facilities containing flammable gases, vapors, combustible dust, or other potentially explosive atmospheres.
Typical applications include:
- Oil and gas processing facilities.
- Chemical plants.
- Fuel storage terminals.
- Hydrogen production facilities.
- Refineries.
- Petrochemical plants.
IEC 60079-14 provides requirements for electrical installation design, equipment selection, installation, and initial inspection in explosive atmospheres.
7.1 Does a 24 VDC Instrument Require Protective Earthing?
A common misunderstanding is that instruments powered by 24 VDC do not require protective earthing.
The supply voltage alone is insufficient to determine the grounding requirements.
Engineers must also consider:
- The power supply and electrical separation arrangement.
- SELV or PELV requirements, where applicable.
- Hazardous area classification.
- Equipment explosion protection concept.
- Equipment certification and special conditions of use.
- Manufacturer’s installation instructions.
- Equipotential bonding requirements.
- Lightning and surge protection requirements.
A low-voltage instrument may still require protective or functional grounding, external bonding, or another connection specified by its certified installation design.
Never remove an existing protective grounding connection simply because the instrument operates at 24 VDC.
7.2 Intrinsic Safety Earthing
Intrinsically safe systems are designed to limit electrical and thermal energy under specified conditions.
Grounding requirements depend on the intrinsic safety architecture and associated apparatus.
For example, certain Zener barriers require a dedicated, reliable intrinsic safety earth connection as specified by their installation instructions.
Galvanically isolated barriers may have different grounding requirements.
These two arrangements must not be treated as interchangeable.
The intrinsic safety system must be installed and maintained according to its certified design and applicable hazardous area requirements.
7.3 Electrostatic and Lightning Protection
Electrostatic grounding helps control the accumulation of electrical charge that could contribute to unwanted discharge.
Lightning protection and surge protection address transient electrical disturbances that may damage equipment or create hazardous conditions.
Outdoor field instruments, storage tanks, long cable routes, and exposed pipelines may require particular attention.
Surge protection devices must be installed with appropriate bonding arrangements and conductor routing according to the approved protection design.
Protective earthing, electrostatic earthing, and lightning protection must be coordinated within the overall plant grounding system.
8. Natural Earthing and Equipotential Bonding

Not every instrument necessarily requires an additional grounding wire if an approved conductive connection already provides the required grounding function.
Certain installations may use electrically continuous metallic structures as part of an engineered grounding or bonding arrangement.
Examples may include:
- Grounded metallic equipment.
- Structural steel.
- Instrument mounting supports.
- Approved metallic bonding conductors.
- Metallic enclosures connected to a grounding network.
However, mechanical contact does not automatically guarantee reliable electrical continuity.
Common problems include:
- Painted mounting surfaces.
- Corroded metal connections.
- Oxidized contact surfaces.
- Loose bolts.
- Insulating gaskets.
- Plastic mounting components.
- Electrically isolated pipeline sections.
These conditions may interrupt the intended grounding path.
Metallic structures should only be used as part of the grounding arrangement when permitted by the applicable design and electrical safety requirements.
Continuity must be verified using appropriate inspection and testing procedures.
8.1 Equipotential Bonding
Equipotential bonding connects conductive parts to reduce potentially hazardous or disruptive voltage differences.
Typical examples include bonding between control cabinet doors, side panels, enclosure frames, and approved grounding busbars.
Flexible bonding straps may be used where required to maintain electrical continuity across moving or removable components.
Such bonding serves a different purpose from arbitrarily connecting multiple instrument housings through a single grounding conductor.
Both arrangements must be evaluated according to their intended electrical function.
9. Common Instrument Grounding Problems and Troubleshooting
Grounding-related problems can affect different types of industrial instruments in different ways.
9.1 Electromagnetic Flow Meters
Electromagnetic flow meters measure the voltage generated when an electrically conductive liquid moves through a magnetic field.
Because the induced measurement signal can be relatively small, proper process potential equalization is important.
Possible grounding-related symptoms include:
- Unstable flow readings.
- Zero-point fluctuations.
- Measurement deviations.
- Increased electrical noise.
Particular attention should be given to installations involving:
- Plastic pipelines.
- Rubber-lined pipelines.
- PTFE-lined pipelines.
- Electrically isolated pipe sections.
- Pipelines with cathodic protection systems.
Depending on the meter design, grounding rings, reference electrodes, or other approved potential equalization arrangements may be necessary.
It is important to distinguish between the protective grounding of the meter housing and the electrical reference required for measuring the conductive liquid.
Cathodically protected pipelines require special consideration because an incorrect grounding connection may interfere with the pipeline protection system.
9.2 Pressure and Differential Pressure Transmitters
Pressure transmitters may experience unstable readings due to electrical interference, poor shielding, or excessive common-mode voltage.
Potential symptoms include:
- Fluctuating 4–20 mA output.
- Unstable DCS readings.
- Intermittent communication problems.
- Unexpected signal noise.
Before concluding that grounding is responsible, check the actual process pressure, power supply, signal wiring, transmitter configuration, and impulse line condition.
9.3 Radar Level Transmitters
Radar level transmitters are widely used in storage tanks, process vessels, and other level measurement applications.
Outdoor installations may be exposed to lightning-induced surges and electrical potential differences.
Appropriate grounding, equipotential bonding, and surge protection can help improve system reliability.
However, unstable radar level readings may also result from process conditions such as foam, condensation, internal obstructions, antenna contamination, or incorrect configuration.
Grounding should be included in the diagnostic process rather than assumed to be the only cause.
9.4 Temperature Instruments
RTDs and thermocouples may produce relatively low-level electrical signals that are sensitive to certain types of electrical interference.
Improper cable routing, shielding, grounding, or signal isolation may contribute to:
- Temperature reading fluctuations.
- Unexpected measurement offsets.
- Intermittent signal disturbances.
When troubleshooting temperature measurement problems, also check sensor condition, wiring configuration, thermocouple extension cables, terminal connections, and transmitter settings.
9.5 PLC and DCS Communication Systems
Incorrect grounding and bonding arrangements may contribute to communication disturbances between field instruments, PLCs, remote I/O modules, and DCS equipment.
Possible symptoms include:
- RS485 communication timeouts.
- Intermittent loss of communication.
- Analog input fluctuations.
- Unstable data transmission.
- Equipment resets following electrical disturbances.
Communication problems should be investigated systematically, including cable routing, termination resistors, network configuration, signal reference connections, shielding, power supply, and equipotential bonding.
10. Practical Grounding Troubleshooting Reference

The following table summarizes common symptoms and possible inspection areas.
| Observed symptom | Possible grounding-related issue | Other factors to investigate |
|---|---|---|
| Electromagnetic flow reading fluctuates | Inadequate process potential equalization | Air bubbles, partially filled pipe, conductivity |
| Pressure signal becomes unstable | Ground loop or electrical interference | Process pulsation, impulse line blockage |
| Temperature reading fluctuates | Shielding or signal reference problem | Sensor damage, wiring, loose terminals |
| Radar transmitter communication fails | Surge damage or bonding problem | Power supply, communication settings |
| RS485 network experiences timeouts | Excessive potential differences or incorrect shielding | Network topology, termination, baud rate |
| Signal becomes unstable when a VFD starts | Electromagnetic interference | Cable separation, power quality, signal isolation |
Grounding is only one possible cause of these symptoms.
A reliable diagnosis requires comparing field measurements, control system trends, operating conditions, and electrical installation details.
Never disconnect a required protective earth conductor as an experimental troubleshooting method.
11. Instrument Grounding Installation Checklist
Before commissioning an industrial instrumentation system, qualified personnel should verify the following items.
Protective Earthing
- Confirm that instrument housings are grounded or bonded as required.
- Verify conductor sizes against the approved design.
- Check terminals for corrosion, looseness, and mechanical damage.
- Verify protective path continuity.
- Confirm that instrument removal will not compromise other required protective connections.
Signal and Cable Shielding
- Identify grounded and isolated signal circuits.
- Follow the manufacturer’s shield termination instructions.
- Avoid unintended signal reference connections.
- Verify cable shield continuity where required.
- Maintain appropriate separation between signal and power cables.
Hazardous Area Installations
- Confirm equipment certification and installation requirements.
- Verify the applicable intrinsic safety earthing arrangement.
- Check cable glands and armour bonding.
- Confirm equipotential bonding requirements.
- Inspect lightning and surge protection arrangements.
Commissioning and Documentation
- Review grounding drawings and installation records.
- Perform the required electrical continuity tests.
- Verify grounding and bonding measurements against project acceptance criteria.
- Record inspection and test results.
- Investigate abnormal instrument signals before final acceptance.
There is no single grounding resistance value or conductor size that can be applied universally to every instrument installation.
Acceptance criteria must follow the applicable standards, protective system design, equipment requirements, and approved project documentation.
Grounding tests and modifications must be carried out by qualified personnel using appropriate isolation, work permits, and electrical safety procedures.
12. Frequently Asked Questions
Can three field instruments share one grounding conductor?
Certain standards and approved designs may permit limited daisy-chained grounding arrangements. However, three instruments should not be treated as a universal allowance. The protective path, conductor capacity, connection reliability, and applicable regulations must be evaluated.
Must every 4–20 mA circuit be grounded?
No. Some circuits require a defined reference connection, while others are designed for isolated or floating operation. Follow the transmitter and control system documentation.
Should cable shields always be grounded at one end?
No. Single-end shielding is commonly used for certain analog circuits, while both-end or multipoint bonding may be appropriate for other communication and EMC applications.
Does mounting an instrument on a steel pipe eliminate the need for a grounding wire?
Not necessarily. Mechanical installation does not guarantee electrical continuity. The connection must satisfy the approved grounding design and applicable safety requirements.
Is a 24 VDC instrument automatically exempt from grounding?
No. Grounding requirements depend on the equipment design, electrical supply arrangement, hazardous area classification, certification, and installation requirements.
Can poor grounding cause inaccurate electromagnetic flow measurements?
Yes. Inadequate process potential equalization and electrical interference may affect electromagnetic flow measurement. However, other process and installation factors must also be investigated.
13. Final Recommendations: Grounding Is a Complete Electrical Path, Not Just a Wire

Industrial instrument grounding should never be reduced to a simple rule about whether instruments can be connected in a chain.
Protective earthing, functional earthing, cable shielding, intrinsic safety earthing, electrostatic protection, and lightning protection serve different purposes.
Each connection must be evaluated according to its intended function and the overall electrical system design.
The most important principles are:
- Maintain reliable protective grounding continuity.
- Avoid unintended signal reference connections.
- Select cable shield termination according to the application.
- Verify electrical continuity when using metallic structures.
- Follow hazardous area certification and installation requirements.
- Coordinate grounding with the plant’s overall bonding and surge protection system.
A visible green-and-yellow grounding wire does not automatically prove that an instrument is properly grounded.
What matters is the reliability and effectiveness of the complete electrical path.
Good grounding design supports personnel safety, accurate measurement, stable communication, and long-term instrument reliability.
Need Reliable Industrial Instrumentation and Technical Installation Support?
Zero Instrument supplies industrial measurement instruments for water treatment, chemical processing, oil and gas, energy, and other industrial applications.
Our product range includes electromagnetic flow meters, Coriolis mass flow meters, pressure transmitters, differential pressure transmitters, radar level transmitters, temperature sensors, and other process measurement instruments.
For instrument selection and installation, our team can help evaluate your application conditions, signal requirements, communication interfaces, and product-specific grounding considerations.
Contact Zero Instrument for assistance with your industrial instrumentation project.
Technical Note: This article provides general engineering guidance. It is not a substitute for applicable electrical regulations, hazardous area requirements, official standards, certified equipment installation instructions, or approved project-specific grounding designs.
Technical References:
- SH/T 3081-2025 — Design Specification for Instrumentation Earthing in Petrochemical Engineering.
- IEC 60079-14:2024 — Explosive Atmospheres: Electrical Installation Design, Selection and Installation of Equipment, Including Initial Inspection.
- Siemens SIMATIC NET PROFIBUS Network Manual — Cable Shielding and Equipotential Bonding.
- Applicable instrument manufacturer installation and grounding documentation.